In order to demonstrate the feasibility of the developed approach, a case
when the mitigating loop is placed at the ground level is thoroughly studied. A flat
configuration of 230 KV transmission line has been used and effect of mitigation at
seven different locations within the right-of-way has been scrutinized and the related
figures and Tables are illustrated. The loop voltage, which is the result of induced
fluxes, is determined. Implementation of the previously derived equation results in
achieving the value of the mitigating loop impedance. The correlation between the three
types of magnetic fields has also been investigated. Finally, a comparative method when
the auxiliary mitigating loop is installed above, below and at the ground level is also
established and the result is shown in a Table