Mitigating magnetic field is caused by the mitigating current in the auxiliary
mitigating loop. This current is achieved by dividing the mitigating loop voltage by the
mitigating loop impedance. The mitigating loop voltage is the result of the flux induced
by each phase of the three phases of the transmission line.
In this chapter, the flux induced by each phase has been thoroughly investigated and the
geometrical location of the auxiliary mitigating loop with respect to the power line has
been scrutinized and the related equations are established. The vector sum of these three
fluxes results in obtaining the total flux penetrating through the mitigating loop and the
corresponding equation is set. Finally, an equation to calculate the mitigating loop
voltage is developed. It is worth mentioning that phases A, B, and C are at 0°, -120° and
+120° respectively.